Other Control Valves |
|
|
|
| PRESSURE SUSTAINING VALVE |
|
TOP
|
| SOLENOID CONTROL VALVE |
 |
Solenoid control valve is a kind of isolation valve, which can
substitute traditional gate valves, ball valves and butterfly valves,
The gate functioning is easily controlled by electrical power.
The valve can be installed in fire control facility, water supply,
or distaunt location where it's difficult to control the gate opening.
The controller is directly fixed and can be easily installed on piping site.
Interchangeable between manual and solenoid control. |
TOP
|
DIRECT- ACTIVATED PRESSURE REDUCING VALVE
(STALINLESS STEEL 316/ Thread Type ) |
|
|
- Valve Body is made by Stainless Steel #316, suitable for fluid, and Vapor.
- The gate is designed for opening status, which will not influence the water supply function under unstable inlet pressure condition.
- When the outlet pressure responds directly to the pressure control chamber and adjusts the setting pressure, it responds quickly and adjusts the pressures accurately.
- Design of piston and disphragm improves the inability of sustaining pressure and leakage.
|

 |
|
| Applied condition of Direct-activated Pressure Reducing Vales : |
- Installing pressure reducing valve directly in sub-pipe can reduce fluid pressure inside the pipe.
- Installing a filter in the inlet of pressure reducing valve can prevent block of valve gate casued by
impurities and limescale.
- Installing pressure relief valve downstream pressure reducing valve can protect the system.
- While using screws to connect pressure reducing vlave, joints should be installed in the inlet and
outlet to make maintainance easy.
|
 |
| Pressure Setting and Flow Rate of Direct-activated Pressure Reducing Vales : |
- Direct-activated pressure reducing valve directly opens and closes the valve gate by the outlet pressure.
When outlet pressure is under setting pressure, valve gate automatically opens.
To make valve gate fully open, adjustable pressure range and setting pressure are relative points.
- A : Pressure drop needed for fully-opened valve gate = B/4 ,B=Adjustable Pressure Range
Maximum-Minimum
B: Adjustable Pressure Range ( = Maximun Minimum Adjustable Pressure Rang )
C: Setting Pressure of Outlet
P: Pressure of fully-opened outlet valve gate, P=C-A
Example:
- Pressure drop needed for fully-opened valve gate for adjusting pressure range 3~9 kgf/cm2 of
direct-activated pressure reducing valve.
A=B/4=9-3/4=1.5 kgf/cm2
If the setting pressure of outlet is 6 kgf/cm2 , pressure of fully-opened valve gate will be
P=6-1.5=4.5 kgf/cm2 ( Outlet pressure should go down under 4.5 kgf/cm2 to make valve gate fully open )
|
| |
| |
 |
TOP
|
| |